Find Switch-Rated Plugs and Receptacles from Meltric
It's a Switch
Meltric DECONTACTOR Series Plugs and Receptacles are approved as an NEC 'Line of Sight' Disconnect
- UL Subject 2682 - Branch Circuit Disconnect Switch
- Motor Circuit Disconnect Switch
It's a Plug & Receptacle
Superior Safety w/ Dead Front Construction
- UL 1682 & UL 1686
- CSA C22.2 No. 182.1
It's the World's Only UL 'SWITCH RATED PLUG & RECEPTACLE'
UL Subject 2682 is a new standard that UL has established for products, like Meltric's DECONTACTOR Series, that provide the performance and capabilities of disconnect switching capabilities from UL 98 (Enclosed & Dead Front Switches) and UL 508 (Industrial Control Equipment) with the plug & receptacle requirements in UL 1682.
| Key Performance Test - UL Subject 2682 - Switch Rated Plugs & Receptacles | |
|---|---|
| Short-Circuit Withstand: | ≥ 10kA (pf = .40 - .50) |
| Short-Circuit Make: | ≥ 10kA (pf = .40 - .50) |
| Overload-Locked Rotor: | 50 operations @ 600% of full load motor current (pf = .40 - .50) |
| Overload-General Use Devices: | 50 operations @ 150% of rated current (pf = .75 - .80) |
| Temperature Rise: | < 30°C |
| Voltage Withstand: | 1000 V + 200% of rated voltage |
| Electrical Endurance: | 6000 cycles @ rated current & voltage (pf = .75 - .80) |
| Mechanical Endurance: | 4000 cycles |